1Vermont Castings DefiantHomeowner’sInstallation andOperatingManualFor use in theUnited States and CanadaSAFETY NOTICE: IF THIS APPLIANCE IS NOT PROPE
10Vermont Castings DefiantNOTE: Do not vent your Defiant into a factory-built(zero-clearance) fireplace. These appliances and theirchimneys are specif
11Vermont Castings DefiantKeep the Stove a Safe Distance fromSurrounding MaterialsBoth a stove and its chimney connector radiateheat in all directions
12Vermont Castings DefiantDefiant Clearance Chartfor use with either a 6” or 8” flue collar/chimney connectionStove ClearanceStove InstalledParallel t
13Vermont Castings DefiantTop Exit Installations, no heat shieldsDefiant Clearance Diagramsfor use with either a 6” or 8” flue collar/chimney connecti
14Vermont Castings DefiantDEFIANT48"(1220mm)48"(1220mm)48"(1220mm)Fig. 13 Parallel installation with rear wall pass-through, twowall s
15Vermont Castings DefiantDistance from the Center of the Flue Collar to the WallThe information on this page is helpful in planning stove placement,
16Vermont Castings DefiantSet Up Your StoveCast iron stoves are heavy, and it will take two tofour people to move your Defiant into position.Wipe the
17Vermont Castings DefiantAssemble the Removable Insert HandleThe white removable insert handle opens and closesthe front doors. Remove after each use
18Vermont Castings DefiantA Damper Directs Air FlowWithin the StoveThe damper handle on the left side of the stoveoperates the damper to direct air fl
19Vermont Castings DefiantWARNING: FIREPLACE STOVES EQUIPPED WITHDOORS SHOULD BE OPERATED ONLY WITHDOORS FULLY OPEN OR DOORS FULLY CLOSED.IF DOORS AR
2Vermont Castings DefiantThis manual describes the installation, operation, and maintenance of the Vermont Castings Defiant Model 1910catalytic-equipp
20Vermont Castings DefiantUse the Air Control Settings that Work Best for YouNo single air control setting will fit every situation.Each installation
21Vermont Castings DefiantIn general, the fire must be sufficiently well-established to ensure that catalytic activity is initiated.When first startin
22Vermont Castings Defiant5. Close the damper when the griddle temperaturereaches 450°F (230˚C).6. Adjust the air control for your desired heatoutpu
23Vermont Castings Defiantlikely to glow at its higher temperatures, which itreaches when the firebox is in its lower range - thecatalyst is an afterb
24Vermont Castings DefiantDRAFT MANAGEMENTA stove is part of a system, which includes thechimney, the operator, the fuel, and the home. Theother part
25Vermont Castings DefiantThere should be no more than eight feet of single-wall stove pipe between the stove and a chimney;longer runs can cool the s
26Vermont Castings DefiantNegative PressureGood draft also depends on a supply of air to thestove; a chimney can’t pull in more air than is availablet
27Vermont Castings DefiantKeep Your Stove Looking New andWorking Its BestLet the fire in the stove go out and allow the stove tocool completely before
28Vermont Castings DefiantCheck the Operation of thePrimary Air ShutterThe primary air shutter is at the back of the ashdrop and is visible from the b
29Vermont Castings DefiantThe Catalytic ElementThis wood heater contains a catalytic combustor,which needs periodic inspection and replacement forprop
3Vermont Castings DefiantTable of ContentsSpecifications ... 4Installation ...
30Vermont Castings DefiantAlignment NotchesLeft WedgeBrick GuideBrick ClipBricksST556Fig. 37 Remove the bricks and the brick retainer.Right WedgeLowe
31Vermont Castings Defiant6. If the element is in good condition and clean, re-install it in the stove and replace the refractoryaccess cover.7. Repla
32Vermont Castings Defiant7. Press the gasketed part firmly against its normalmating surface to seat the gasket evenly in its channel.Close and latch
33Vermont Castings DefiantAppendix: Catalytic CombustorIn any chemical reaction, including the combustionprocess, there are certain conditions which
34Vermont Castings DefiantAppendix: Chimney and Fireplace HazardsGeneral -A. Improper chimney height. The top of the chimneymust be at least 3 feet hi
35Vermont Castings Defiant8513291236481626171851446474964667283436374041482711303133841067424457584366528535655961738180837476457071545679808253515588
36Vermont Castings DefiantItem/Model Number Part NumberDefiant (continued)13. Left Griddle Quadrant 130180714. Right Griddle Quadrant 130183216. Gridd
37Vermont Castings DefiantWarrantyLimited 3 Year WarrantyThe Vermont Castings Majestic Products Company warrants thatthis woodburning stove will be fr
38Vermont Castings Defiant410 Admiral Blvd. • Mississauga, Ontario, Canada L5T 2N6 • 905-670-7885www.majesticproducts.com • www.vermontcastings.comThe
4Vermont Castings DefiantSpecificationsDefiant, Model 1910Range of heat output... 10,600 to 44,400 Btu’s/hr.*Maximum heat output...
5Vermont Castings DefiantInstallationSAFETY NOTICE: IF YOUR DEFIANT IS NOTPROPERLY INSTALLED, A HOUSE FIRE MAYRESULT. TO REDUCE THE RISK OF FIRE,FO
6Vermont Castings DefiantWhat Kind of Chimney to UseYou must connect the Defiant to a code-approvedmasonry chimney with a flue liner, to a relined mas
7Vermont Castings DefiantAccessories to help make the connection betweenstainless steel chimney liners and your Defiant areavailable through your loca
8Vermont Castings DefiantSecuring the Single-wall Connector to aMasonry ChimneyBoth freestanding masonry chimneys and fireplacemasonry chimneys may be
9Vermont Castings DefiantIf the chimney connector in your installation entersthe chimney above a fireplace, follow all the guidelinesmentioned above f